TAM-H-RCH-011 · Human · Reach: What they can touch · New in TAM
Engineering Workstation Seat
Access to the engineering workstation lets a person change PLC logic and process settings in an industrial plant.
In OT environments, the engineering workstation runs the vendor software that programs controllers, such as Siemens TIA Portal, Rockwell Studio 5000 or Schneider EcoStruxure. Whoever can log on to it, locally or through a jump host, can upload, change and download controller logic.
These machines are often shared, with a common local account, old Windows builds, and no per-user logging. Many plants keep PLCs in remote or program mode so engineers can push changes without walking to the cabinet.
That combination means one disgruntled technician or contractor can change how physical equipment behaves, and the plant may only be able to say that someone at that workstation did it.
What it looks like
- A contractor keeps a remote access account to the plant jump host after the project closes.
- Several technicians share one Windows account on the engineering workstation.
- PLC key switches are left in REM mode, so logic can be downloaded without anyone on the floor.
Detections (2)
- DET-040Engineering Workstation Sessions Off ScheduleFlag logons to OT engineering workstations and jump hosts outside planned work windows.Confidence MediumWindowsNetwork
- DET-098PLC Program Downloads and Mode ChangesAlert on controller logic downloads, online edits and mode changes seen on the OT network.Confidence HighNetwork
Controls (2)
- CTL-049Hardened Engineering WorkstationsGive each engineer a named login on hardened engineering workstations reached only through a recorded jump host.TechnicalEffort HighEffect High
- CTL-110Two-Person Rule in the PlantRequire a second person to approve and witness controller logic downloads and critical setpoint changes.ProcessEffort MediumEffect High