DET-134 · human · confidence Medium
Setpoint and Alarm Limit Drift
Compare setpoint and alarm-limit changes in the historian and HMI audit trail against approved ranges.
Process historians and HMI audit trails record who changed which tag and to what value. Defining an approved range for critical setpoints and alarm limits, and alerting on values outside it or on alarm limits widened in the same session as a setpoint change, catches both sabotage and dangerous mistakes.
Ask process engineers to set the ranges, since they know which tags matter. Repeated small changes by one person across shifts can be as telling as one large change.
- Data sources
- Process historian (for example OSIsoft PI or AVEVA)HMI audit trailOT network monitoring
- Platforms
- Network
Logic
SELECT tag, user, old_value, new_value, ts
FROM hmi_audit a JOIN tag_limits l USING (tag)
WHERE (new_value > l.max_ok OR new_value < l.min_ok)
OR (tag LIKE '%_ALM_HI' AND new_value > old_value AND EXISTS (
SELECT 1 FROM hmi_audit b WHERE b.user = a.user AND b.tag = replace(a.tag, '_ALM_HI', '_SP') AND abs(b.ts - a.ts) < interval '30 min'))False positives
Product changeovers and recipe changes that legitimately move setpoints.